Reference: Modbus Registers
This section provides the default register mapping for WAGO energy analyzers. Ensure your device configuration matches these addresses for accurate data visualization.
Standard Energy Meter Registers (879 Series)​
| Register Address | Parameter | Data Type | Units |
|---|---|---|---|
0x0002 | Phase 1 Voltage | Float32 | V |
0x0004 | Phase 2 Voltage | Float32 | V |
0x0006 | Phase 3 Voltage | Float32 | V |
0x0008 | Phase 1 Current | Float32 | A |
0x000A | Total Active Power | Float32 | W |
0x0010 | Total Active Energy | Float32 | kWh |
[!IMPORTANT] WEVA uses Zero-Based Addressing. If your device manual uses 1-based addressing, subtract 1 from the register address in the configuration.
Writable Control Registers​
Admins can modify these registers via the Control interface.
| Register Address | Function | Range | Default |
|---|---|---|---|
0x1000 | Alarm Threshold (High) | 0 - 5000 | 4500 |
0x1002 | Reset Energy Counter | 1 = Reset | 0 |
Troubleshooting Data Accuracy​
If values appear distorted (e.g., massive numbers):
- Verify the Byte Order in the device settings (Standard: Big Endian).
- Ensure the correct Register Function Code (03 for Read Holding, 04 for Read Input) is selected.
Screenshot: View of a Modbus scanner tool showing matching registers with WEVA.